DSpace
 

EPrints@IIT Delhi >
Faculty Research Publicatons  >
Electrical Engineering >

Please use this identifier to cite or link to this item: http://eprint.iitd.ac.in/handle/2074/1601

Title: Discrete-mode automatic generation control of a two-area reheat thermal system with new area control error
Authors: Kothari, M L
Nanda, J
Kothari, D P
Das, D
Keywords: discrete-mode
reheat thermal system
guarantees zero steady-state
Issue Date: 1989
Citation: Power Systems, IEEE Transactions on, 4, 2730 - 738
Abstract: The authors deal with discrete-mode automatic generation control of an interconnected reheat thermal system considering a new area control error (ACE) based on tie-power deviation, frequency deviation, time error, and inadvertent interchange. Optimum integral and proportional integral controllers using the concept of stability and ISE techniques have been obtained with conventional ACE and the present ACE, and their dynamic performances are compared for a step load perturbation. Results reveal that the regulator based on the present ACE concept always guarantees zero steady-state time error and inadvertent interchange, unlike a controller based on conventional ACE. The settling time for tie-power and frequency deviations is, however, somewhat longer with the controller based on the present ACE
URI: http://eprint.iitd.ac.in/dspace/handle/2074/1601
Appears in Collections:Electrical Engineering

Files in This Item:

File Description SizeFormat
kothridis1989.pdf121.56 kBAdobe PDFView/Open
View Statistics