eprints
 

EPrints@IIT Delhi  >
Faculty Research Publicatons  >
Electrical Engineering >

Please use this identifier to cite or link to this item: http://hdl.handle.net/2074/1913

Full metadata record

DC FieldValueLanguage
contributor.authorSingh, B-
contributor.authorAl-Haddad, K-
contributor.authorChandra, A-
date.accessioned2006-07-03T03:59:53Z-
date.available2006-07-03T03:59:53Z-
date.issued1998-
identifier.citationPower Systems, IEEE Transactions on, 13(1), 133 - 138p.en
identifier.urihttp://eprint.iitd.ac.in/dspace/handle/2074/1913-
description.abstractThis paper deals with a new control scheme for a parallel 3-phase active filter to eliminate harmonics and to compensate the reactive power of the nonlinear loads. A 3-phase voltage source inverter bridge with a DC bus capacitor is used as an active filter (AF). A hysteresis based carrierless PWM current control is employed to derive the switching signals to the AF. Source reference currents are derived using load currents, DC bus voltage and source voltage. The command currents of the AF are derived using source reference and load currents. A 3-phase diode rectifier with capacitive loading is employed as the nonlinear load. The AF is found effective to meet IEEE-519 standard recommendations on the harmonics levelen
format.extent71379 bytes-
format.mimetypeapplication/pdf-
language.isoenen
subjectparallel 3-phaseen
subjectactive filteren
subjectdiode rectifieren
titleA new control approach to three-phase active filter for harmonics and reactive power compensationen
typeArticleen
Appears in Collections:Electrical Engineering

Files in This Item:

File Description SizeFormat
bhimsinghnew1998.pdf69KbAdobe PDFView/Open