DSpace
 

EPrints@IIT Delhi >
Faculty Research Publicatons  >
Electrical Engineering >

Please use this identifier to cite or link to this item: http://eprint.iitd.ac.in/handle/2074/1947

Full metadata record

DC FieldValueLanguage
dc.contributor.authorRoy, S-
dc.date.accessioned2006-07-03T05:38:53Z-
dc.date.available2006-07-03T05:38:53Z-
dc.date.issued1999-
dc.identifier.citationPower Systems, IEEE Transactions on, 14(3), 935 - 943p.en
dc.identifier.urihttp://eprint.iitd.ac.in/dspace/handle/2074/1947-
dc.description.abstractThis paper introduces a new small perturbation model for the well known “generator/infinite bus” system, that includes explicit representation of amortisseur windings. The major points of difference between this model and the conventional Heffron-Phillips small perturbation model are discussed by a comparison of synchronising and damping torque coefficients obtained from them. The design and tuning requirements of a conventional generator power system stabiliser (PSS), principally intended to damp out local oscillations, are reconsidered to accommodate amortisseur effects as reflected in the new generator model. It is shown that the PSS transfer function may now assume a different generic form, as well as a different set of compensatory time constantsen
dc.format.extent107898 bytes-
dc.format.mimetypeapplication/pdf-
dc.language.isoenen
dc.subjectsmall perturbation analysisen
dc.subjectlocal oscillationsen
dc.subjectpower system stabiliseren
dc.titleInfluence of amortisseurs on stabiliser design requirements for damping local oscillations of a generatoren
dc.typeArticleen
Appears in Collections:Electrical Engineering

Files in This Item:

File Description SizeFormat
royinf1999.pdf105.37 kBAdobe PDFView/Open
View Statistics

Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.

 

Valid XHTML 1.0! DSpace Software Copyright © 2002-2010  Duraspace - Feedback